Electrical System Protection
Electrical system protection is essential to ensure personal safety and prevent damage to property and equipment. It relies primarily on the use of specific safety devices and compliance with the CEI 64-8 and IEC 60364 standards.
The main protection devices installed in the electrical panel are:
Magnetic Circuit Breaker: protects the system from overcurrents, including overloads (when too many devices are connected to a circuit) and short circuits (a sudden, excessive flow of current). Every portion of the system downstream of the circuit breaker is protected from these risks.
Residual Current Device (RCD): protects people from indirect contact and the risk of electrocution. It trips when it detects a current leakage to ground (a difference between the current entering and leaving the circuit), often caused by an insulation fault or accidental contact between a person and a live part.
Residual Current Circuit Breaker: combines both functions in a single device, offering protection against both overcurrents and leakage currents (indirect contacts).
Surge Protection Devices (SPDs): protect systems and sensitive equipment from transient overvoltages, often caused by lightning strikes or power failures.
These devices and compliance with the standards ensure the safe use of electricity.
The construction and maintenance of electrical systems in Italy must comply with specific standards:
• CEI 64-8 Standard: This is the primary technical reference for the proper construction of electrical systems. It specifies the minimum safety and efficiency requirements for residential and industrial systems.
• IEC 60364 Standard
Residual Current Device (RCD)
|
The vector sum of the currents flowing through the live conductors (including the neutral if present) of a circuit, which is zero under normal insulation conditions, assumes values greater than zero when a ground fault occurs and is called the ground fault current or differential current IΔ.
The RCD is a device sensitive to the sum of these currents and capable of tripping when a ground leakage current occurs.
It consists of a toroidal transformer in which, under normal operating conditions, the resulting flux due to the currents flowing through the circuit is zero (under normal conditions, when the difference between the incoming and outgoing currents is zero, the magnetic flux in the toroid is zero, while in the event of a ground fault, when the difference between the two currents (called differential current) is no longer zero, a flux is created in the toroid's magnetic circuit).
When an insulation fault occurs, for example, phase-to-ground, the resulting flux is no longer zero and induces, on an appropriate secondary winding, an electromotive force capable of causing, through the intervention of the differential relay, the opening of the circuit breaker.
|
 |
 |
 |
Main definitions and operating characteristics
Rated current (In)
This is the current value that the device is capable of carrying uninterruptedly.
Rated residual current tripping current (IΔn)
This is the current value assigned by the manufacturer to a specific circuit breaker that has or integrates residual current protection. The circuit breaker must operate according to this value under the conditions specified by the standards.
Rated residual current non-tripping current (IΔno)
This is the current value assigned by the manufacturer and indicated by the standards as 50% of IΔn, for which the residual current circuit breaker must not trip under the conditions defined by the standards themselves.
Rated residual making and breaking capacity (IΔm)
This is the value of the alternating component of the residual current that the circuit breaker can establish, carry, and interrupt under the conditions specified by the standards. The standards establish that the minimum value must be chosen between 10In and 500 A, with the higher value being chosen.
Rated Making and Breaking Capacity (Im)
This is the effective value of the alternating component of the prospective current, assigned by the manufacturer, that a residual current circuit breaker (RCCB) can make, carry, and break under specified conditions. The minimum value of Im is 10 In or 500 A, whichever is higher.
Rated Conditional Short-Circuit Current (Inc)
This is the short-circuit current value that a RCCB compliant with the IEC 61008 standard can withstand without degrading its performance or compromising its functionality when coordinated with a circuit breaker or fuse (SCPD - Short Circuit Protective Device) capable of providing additional protection against overcurrents.
Rated Conditional Residual Current (IΔc)
This is the prospective residual current value that the RCCB, properly coordinated with an appropriate SCPD, can withstand without suffering damage that would jeopardize its proper function. This is a characteristic parameter of RCDs without built-in overcurrent releases (pure RCDs).
AC type operating characteristic
These circuit breakers operate correctly within the limits established by standards only in the presence of alternating ground fault currents.
A type operating characteristic
These circuit breakers operate correctly within the limits established by standards in the presence of both alternating ground fault currents and alternating currents with unidirectional pulsating components applied instantaneously or slowly increasing.
B type operating characteristic
These circuit breakers operate correctly within the limits established by standards in the presence of both alternating ground fault currents and alternating currents with unidirectional continuous components.
Differential switches of type AC, A, B, F
 |
 |
| There are four types of RCDs: AC, A, F, and B. Below, we'll analyze the differences and the criteria for choosing one. Finally, we'll explore the use of RCDs in medical facilities and elevators with variable-speed drives (inverters). |
|
Indirect Contact
An "indirect contact" is the contact of people with a live earth due to a fault. A live earth is the conductive part of an electrical component that can be touched and is not live under normal conditions, but can become live under fault conditions.
An example is the external metal frame of a washing machine, which can become live if a power cable inside comes loose from its terminal and touches the metal casing.
This creates a danger for a person who inadvertently touches the live metal frame, as the difference in voltage between the hand in contact with the live part and the feet (theoretically at zero potential) causes a current to flow through the body, which can cause serious injury, even death.
The standard establishes that the maximum contact voltage in the event of a fault must be 50V (or 25V in specific environments, such as medical facilities).
To protect people from indirect contact, the CEI 64-8 standard requires the presence of a circuit breaker capable of automatically interrupting the power supply in the event of a fault within a short time (a few tenths of a second). In TT systems, devices suitable for automatically disconnecting the power supply and capable of detecting ground fault currents are residual current circuit breakers (also called lifesavers).
|
The RCD is a device that measures the difference between the incoming and outgoing currents in the protected circuit. It trips when a difference between the two currents occurs. In fact, in the absence of faults, the current flowing to the load is the same as the current flowing back. When a ground fault current occurs, the two currents become different, generating a variable magnetic flux that creates an induced voltage in the residual current coil inside the circuit breaker, and a corresponding force that causes the circuit breaker's opening control device to trip.
The first to be introduced on the market and still the most widely used were AC-type residual current devices, indicated by the symbol in the table below.
They are suitable for detecting alternating differential current at a mains frequency of 50 Hz and are suitable for linear loads, such as traditional light bulbs or electric heaters without control electronics.
In recent years, the presence of nonlinear electronic circuits, such as rectifiers, switching power supplies, and inverters, once typical of industrial appliances, has become increasingly widespread in household appliances as well. Nonlinear circuits ensure that in the event of a fault, or even in the absence of a fault, the differential current flowing on the protective cable is not sinusoidal in shape as would be the case with linear circuits, but is distorted by the presence of DC and high-frequency components.
Currents with direct current components compromise the operation of standard AC-type residual current devices, as ground fault currents are not detected by the toroidal transformer.
As a result, the technology of residual current circuit breakers has also evolved, capable of detecting and interrupting increasingly complex residual currents.
The AC-type circuit breakers were followed by Type A, Type B, and Type F circuit breakers.
Type A Differential switch (Residual Current Device)
Type A RCDs also detect and interrupt pulsating unidirectional currents of both polarities, including those partially or superimposed on a DC component of up to 6 mA. These are the typical forms of earth fault currents in single-phase appliances containing diodes, various types of rectifier bridges, dimmers for LEDs, etc.
This does not mean that Type A RCDs detect DC residual current, but that the presence of a DC component of up to 6 mA will not alter the behavior of the RCD. The value of 6 mA is the maximum permitted DC fault current for appliances equipped with a household plug (IEC 61140).
Type F Differential switch (Residual Current Device)
Type F residual current devices, an evolution of the Type A, also have the ability to detect and interrupt multi-frequency residual currents, meaning those with multiple frequencies in addition to the mains frequency. These are the typical designs of single-phase variable-frequency inverters used to drive motors, now commonly used in various household appliances such as washing machines, air conditioners, and heat pumps.
Immunity to direct residual current is increased to 10 mA. Furthermore, type F residual current devices have high immunity to interference (withstand short-duration current pulses), helping to solve the annoying problem of nuisance tripping that modern household appliances contribute to.
Type B Differential switch (Residual Current Device)
The Type B residual current device further extends performance and can cover virtually any application. In fact, Type B circuit breakers are also sensitive to ripple-free DC residual current, positive or negative, AC residual current up to 1 kHz, the superposition of AC and DC residual current, and residual current from two-phase and three-phase rectifiers.
Applications are predominantly, but not exclusively, three-phase and include motor drive inverters, static converters in general, electric vehicle charging systems, biomedical equipment, photovoltaic systems, and energy storage systems.
Choosing a Residual Current Device
When choosing the type of RCD (residual current device), the installer or system designer must take into account the potential fault current caused by the appliances they intend to power. An RCD that is unsuitable for the loads can lead to unpleasant consequences of varying severity, ranging from untimely tripping to delayed or no tripping in the event of a fault.
In general, it is necessary to follow the information or recommendations of the appliance manufacturers, typically found in the user and maintenance manuals.
The following table summarizes the main cases where Italian regulations explicitly require or recommend the installation of at least Type A RCDs. In all cases, the term "if RCDs are necessary" is used: for example, in a TN industrial system, protection from indirect contact may not require a RCD, while in a TT system, RCDs are always mandatory.

The Differential switch in Medical Environment
Medical facilities are classified into Group 1 and Group 2 based on the risk associated with the use of medical electrical equipment and the vulnerability of patients.
Group 1 includes clinics with equipment that has parts applied to the body but not in the cardiac area (e.g., pathophysiology, radiology, and hydrotherapy offices).
Group 2 includes high-risk areas such as operating rooms, intensive care units, anesthesia rooms, and cardiac catheterization rooms, where the applied parts are in contact with the cardiac area or are used for vital treatments.
Group 1
Definition:
Places where electromedical equipment with parts applied to the body is used, but not in the patient's cardiac region.
Examples:
• Doctor's offices with equipment with applied parts
• Patient rooms
• Rooms for pathophysiology, hydrotherapy, and radiology examinations
• Delivery rooms
• Dental offices
Group 2
Definition:
Rooms where applied parts are intended for cardiac procedures (intracardiac procedures) or where a power failure could be life-threatening (vital treatments).
Examples:
• Surgical suite
• Anesthesia suite
• Angiography suite
• Intensive care suite
• Premature baby suite
• Postoperative recovery rooms
In medical facilities, electromedical equipment, such as computerized axial tomography (CT) or magnetic resonance imaging (MRI) devices, incorporate electronic circuits that, as previously noted, in the event of a ground fault, generate currents with direct current components that can compromise the operation of standard AC-type residual current devices.
Therefore, Group 1 and Group 2 facilities must use, depending on the type of fault current, either Type A residual current devices (RCDs), capable of tripping even with pulsating unidirectional fault currents, or Type B residual current devices (RCDs), capable of tripping even with pulsating and direct unidirectional fault currents.
The CEI 64-8 standard establishes that the terminal circuits of Group 1 medical facilities, which supply socket outlets with a rated current of up to 32 A, must be protected by RCDs with a rated residual current of no more than 30 mA (additional protection).
In Group 2 premises, all circuits must be protected by a 30 mA residual current device (RCD) if not powered by the IT-M system. The "IT-M system" refers to an earthed electrical system (IT) for medical use, designed to ensure maximum continuity of service in environments such as operating rooms, doctors' offices, and laboratories. It operates with an isolation transformer that prevents the flow of current in the event of a first earth fault, while a permanent insulation monitoring device provides audible and visual warnings of the fault and the need for intervention.
In Group 1 and Group 2 medical facilities, where RCDs are required, only Type A or Type B RCDs should be used, depending on the type of potential fault current.
Therefore, using the example of a dental office, all RCDs protecting circuits and appliances in Group 1 rooms (e.g., dental office, orthopantomography room, etc.) must be Type A or B, depending on the type of equipment.
Paradoxically, and in the author's opinion, this is a loophole in the regulation. If the power supply system is TN, and the electromedical equipment is connected to the system via fixed wiring, RCD protection is not required. Therefore, if the relevant circuit in the panel is protected by a RCD (voluntary protection), the RCD can also be AC.
In Group 2 facilities, all circuits outside of IT-M, regardless of whether they are TT or TN, must be protected with Type A or B RCDs, depending on the type of load.
Residual Current Devices in Elevators
Residual current devices (RCDs) are used to provide insulation fault protection in some residential and industrial installations, in addition to that provided by the installed equipment, such as the variable-speed drive (AVV) of elevators (so-called "inverter control panel").
An insulation fault or direct contact with certain types of AVV circuits can cause a current with a DC component to flow through the protective equipotential conductor, thus reducing the ability of a type A or AC RCD to provide such protection for other equipment in the installation.
Residual Current Circuit Breaker
A residual current circuit breaker (RCB) is an electrical protection device that acts as both a fuse and a circuit breaker. It is a key component of a home or building's electrical panel, ensuring essential electrical safety for domestic electrical systems.
The RCB is designed to interrupt power in the event of an overload or ground fault, thus preventing short circuits, fires, and other electrical hazards. This means that the RCB plays a crucial role in protecting electrical circuits and appliances, as well as protecting people from potential electric shocks.
The RCB is an essential component for the safety of both domestic and industrial electrical systems. Acting simultaneously as a fuse and circuit breaker, the RCB protects against both overloads and ground faults, preventing the risk of short circuits and fires.
The RCD operates on two protections: a magnetic one, which intervenes in the event of overcurrents, and a thermal one, which activates when critical temperatures are reached. When a circuit is overloaded, the RCD interrupts the power supply to prevent overheating. Specifically, an overload occurs when the current exceeds the circuit's capacity, often caused by excessive use of devices on a single outlet. In the event of a ground fault, the RCD detects abnormal current flow due to accidental contact between wires and metal parts, interrupting the power supply to prevent electric shock.
RCDs therefore offer essential protection against overcurrents and ground faults, which are crucial to the safety of electrical systems. Periodic testing using test buttons on the RCD can confirm its operability.
In the design of low-voltage (LV) electrical systems, coordinating protection systems and correctly sizing lines are essential to ensure safety, continuity of service, and regulatory compliance.
The primary objective is to ensure that each system component (conductors, protection devices, loads) operates within the safety limits established by technical standards, primarily CEI 64-8.
The main standards and technical guidelines for the design and coordination of protection systems are:
- CEI 64-8: Electrical user systems with a nominal voltage not exceeding 1000 V in alternating current.
- CEI 0-21: Rules for connection to the LV network.
- CEI 17-13/1: Overcurrent protection devices.
- CEI EN 60947-2 / 60898-1: Automatic circuit breakers.
- CEI EN 60269: Fuses.
- CEI 11-28 and 11-35: Coordination and selectivity criteria.
- CEI UNEL 35024 – Current carrying capacity of electrical cables.
Basic Criteria
Conductor sizing must simultaneously satisfy several criteria related to cable heating, voltage drop across the cable, with standable short-circuit limits, and protection against indirect contact.
| Thermal carrying capacity |
The cable's carrying capacity depends on the electrical load circulating and the maximum current carrying capacity of the cable:
IB ≤ IZ
Where
- IB: circuit operating current
- IZ: cable carrying capacity under continuous operation
Cable carrying capacity ratings are found in tables in the IEC UNEL 35024 standard. The carrying capacity rating is adjusted based on the installation method according to
IZ =K1*K2*Io
- K1: correction factor for temperature
- K2: correction factor for bundled circuits
- Io: cable carrying capacity in air
| Room temperature (Ta in °C) |
k? for insulation 70°C (PVC) |
k? for insulation 90°C (XLPE/EPR) |
| 25 |
1,03 |
1,02 |
| 30 |
1,00 |
1,00 |
| 35 |
0,96 |
0,98 |
| 40 |
0,91 |
0,95 |
| 45 |
0,86 |
0,93 |
| 50 |
0,80 |
0,89 |
| 55 |
0,74 |
0,84 |
| 60 |
0,67 |
0,80 |
| 65 |
0,58 |
0,75 |
| Number of grouped circuits |
factor k? (Multi-core / single-core in tube) |
| 1 |
1,00 |
| 2 |
0,80 |
| 3 |
0,70 |
| 4 |
0,65 |
| 5 |
0,60 |
| 6 |
0,57 |
| 7 |
0,54 |
| 8 |
0,52 |
| 9 |
0,50 |
Extract of the correction factor K1 and K2.

Extract of the value of Io from the normative table for lines with 2 loaded cables and laid in pipes.
The voltage drop between the delivery point and the loads must remain within the limits set by the CEI 64-8 standard (generally ≤ 4% for distribution systems and ≤ 5% for lighting).
ΔV = √3 IB (R cosφ+X sinφ) L
• R: cable resistance per unit length from tables extracted from the CEI 64-8 standard
• X: cable reactance per unit length from tables extracted from the CEI 64-8 standard
• L: line length

Explanatory extract of the value of voltage drops for electrical cables.
The cable must withstand thermal and dynamic stresses due to short circuits. The cross-section must comply with:

Where:
a. Icc: short-circuit current to be calculated
b. t: tripping time of the protective device, the values of which are set by the standard. For all terminal circuits, the values in the CEI 64-8/4 table apply; for all other circuits, times no longer than 5 s are permitted.
c. k: constant dependent on the cable material and insulation, identifiable from the standard table.
| Mandatory Minimum Cross-Sections (CEI 64-8) |
The CEI 64-8 standard requires minimum cross-sections regardless of the load-bearing capacity calculation, to ensure mechanical resistance and suitability for typical loads.
| Line/circuit type |
Maximum protection current |
Minimum section (Copper) |
| Illumination |
16 A max |
1,5 mm² |
| Electrical sockets |
20 A max |
2,5 mm² |
| Power devices (water heater) |
20 A max |
2,5 mm² |
| Oven/plate power supply |
32 A max |
6 mm² |
| Riser (from the meter) |
30 A – 60 A max |
≥ 16 mm² |
| Riser (from the meter) |
90 A max |
≥ 25 mm² |
Design data:
- Three-phase load 15 kW, cosφ = 0.9, 400 V, L = 40 m, installation in copper conduit under plaster.
- Maximum permissible drop: 3%.
1. Operating current:

2. Switch selection:
IN = 25°
3. Cable cross-section (CEI-UNEL 35024 table):
4 mm² → (IZ = 28,A), voltage drop ≈ 2.6% → acceptable.
4. Short circuit protection check:
OK if the expected Icc is within the thermal and mechanical resistance limits.
Objectives of Coordinatio
- Protection of people (against overcurrents and indirect contact);
- Protection of cables and equipment;
- Continuity of service (through selectivity and limitation of let-through energy).
1. Coordination with the Earthing System and Protection against indirect contact
Coordination with the earthing system and protective devices must ensure tripping within the expected timeframe.
The coordination relationship in TN systems is:

Where ( Ia ) is the current that causes automatic tripping within the time limit established by the regulations. The attached table is an extract of the maximum tripping times. The Ia current is identified on the typical tripping curve of magnetothermal devices by cross-referencing it with the maximum tripping time.
| Voltage U? phase-ground (V) |
Terminal circuits (A) |
Maximum interruption time |
| ≥ 230 |
with a rated current ≤63A (if with sockets) or <32A (if with a fixed connection) |
0,4 s |
| ≥ 230 |
distribution circuits and terminal circuits other than those above (e.g. circuits with In > 63A) |
5 s |
The coordination relationship in TT systems becomes:

Where Idn is the RCD tripping current and UL is the limiting contact voltage (50V in ordinary environments and 25V in special environments such as hospitals).
For RCDs, the CEI 64-8 standard defines the following tripping times:
| Circuits |
U? phase-earth voltage (V) |
Maximum interruption time (s) |
| Terminal Circuit |
≥ 50 |
0,2 s |
| Distribution Circuit |
≥ 50 |
1 s |
2. Thermal and magnetic coordination
Ensure that the protective device trips before the cable reaches dangerous temperatures, but must also guarantee the correct operation of the loads. The coordination relationships are:
IB ≤ IN ≤ IZ (1)
If ≤ 1,45 IZ (2)
Where:
- IB: operational current of the circuit
- IN: nominal current of the protective device
- IZ: continuous current carrying capacity of the cable
- If: guaranteed tripping current of the device
(2) is always satisfied in the case of automatic circuit breakers.
In the case of a fuse, If is generally If =1,6*In, so it is necessary to ensure that (2) is satisfied.
3. Coordination between fuses and circuit breakers
In some cases, a combination of devices is used (e.g., upstream fuse, downstream circuit breaker) to ensure protection and energy limitation. In these cases, the fuse becomes a backup protection.
4. Coordination between devices in series (selectivity)
Ensure that in the event of a fault, only the device immediately upstream of the fault trips.
- Time or chronometric selectivity: This is achieved by differentiating the tripping times of the devices; intentionally delay the action of the device at the beginning of the power line compared to the downstream devices.
- Energy or current selectivity: This is achieved by adjusting the tripping currents of the circuit breakers; for lower currents, the downstream device trips; for higher currents, the device at the beginning of the power line trips (selection of differential tripping limits).
- Logic selectivity: Communicating circuit breakers that coordinate digitally.
5. Conclusions
Coordination of protection systems and line sizing are an essential part of electrical design.
Correct application of IEC standards allows you to:
- ensure the safety of people and property;
- preserve the integrity of cables and devices;
- optimize system costs;
- ensure continuity and reliability of the electrical service.
6. References
- IEC 64-8:2021 Standard – Electrical user systems with a rated voltage ≤ 1000 V AC
- IEC 11-35 Guide – Coordination between protection devices.
- IEC EN 60947-2 – Automatic circuit breakers for industrial use.
- IEC EN 60269 – Low voltage fuses.
- IEC UNEL 35024 – Current carrying capacity of electrical cables.