A ground fault, caused by a loss of insulation between a live conductor and an earth, represents a system problem that causes damage to electrical installations and, above all, represents a danger to people; the latter may find themselves in contact with a conductive part that is normally not live but which, due to the fault, is at a dangerous potential.
Useful definitions derived from the standard on electrical consumer systems with a nominal voltage not exceeding 1000V alternating current and 1500V direct current.
|
 |
Below are some useful definitions:
• Touch voltage: Voltage established between simultaneously accessible parts in the event of an insulation failure.
• Total earth voltage: Voltage established following an insulation failure between exposed conductive parts and a sufficiently distant point of zero potential.
• Rated voltage to earth of a system: The nominal voltage to earth is defined as
- in three-phase systems with an isolated neutral or with a neutral grounded through impedance, the nominal voltage;
- in three-phase systems with a neutral directly grounded, the star voltage corresponding to the nominal voltage divided by 3;
- in single-phase or direct current systems without grounding points, the nominal voltage;
- in single-phase or direct current systems, with the midpoint grounded, half the nominal voltage.
• Live part: conductor or conductive part that is live in ordinary service, including the neutral conductor, but excluding, by convention, the PEN conductor.
• Hazardous live part: live part that can give rise under certain conditions of external influences to a dangerous current.
• Ground: conductive part of an electrical component that can be touched and that is not live under ordinary conditions, but that can become live under fault conditions.
• Direct contact: contact of persons with live parts.
• Indirect contact: contact of persons with a ground that is live due to a fault.
• Accessible parts: conductors or conductive parts located in the zone extending from a point or surface ordinarily occupied or traversed by people to the limits that a person can reach with one hand without the use of tools.
• Simultaneously accessible parts: conductors or conductive parts that can be touched simultaneously by a person.
• Earth leakage current: current that, in the absence of a fault, flows to earth or exposed conductive parts.
• Residual current: vector sum of the instantaneous currents flowing through all the live conductors of a circuit at a point in the installation.
• Enclosure: part that provides protection for an electrical component against certain external agents and, in all directions, against direct contact.
• Barrier: part that provides protection against direct contact in the usual directions of access.
• Obstacle: element intended to prevent inadvertent direct contact with live parts, but not to prevent intentional direct contact.
• Basic insulation: insulation of live parts used for basic protection against direct and indirect contact.
• Supplementary insulation: independent insulation provided in addition to the primary insulation to ensure protection against electrical contact in the event of a failure of the primary insulation.
• Double insulation: insulation comprising both the primary insulation and supplementary insulation.
• Reinforced insulation: a unique insulation system applied to live parts, capable of ensuring a degree of protection against electrical contact equivalent to double insulation, under the conditions specified in the relevant standards.
• Insulating floors and walls: floors and walls of rooms whose resistance is high enough to limit the current to a non-dangerous value.
• Earth: the ground as a conductor whose electrical potential at every point is conventionally considered equal to zero.
• Earth electrode: a conducting body or group of conducting bodies in electrical contact with the ground and which establishes an electrical connection to the earth.
• Earth resistance: the resistance between the main earth collector (or node) and the earth.
• Electrically independent earthing systems: earthing systems with separate earth electrodes such that the maximum current that one of these systems can dissipate does not change the potential with respect to earth of the other system by more than a certain value.
• PE protective conductor: conductor required for certain protection measures against indirect contact for the connection of some of the following parts:
- exposed conductive parts;
- foreign conductive parts;
- main earth collector (or node);
- earth electrode;
- source earthing point or artificial neutral.
• PEN conductor: conductor that simultaneously performs the functions of both protective conductor and neutral conductor.
• Earthing system: assembly of earth electrodes, earth conductors, main earth collectors (or nodes), and protective and equipotential conductors, intended to provide protective and/or operational earthing.
• Fault current: Current that occurs following an insulation failure or when the insulation is short-circuited.
• Ground fault current: Fault current that flows through the earthing system.
• Expert person: Person with sufficient technical knowledge or experience to enable them to prevent the hazards that electricity may present.
• Informed person: Person adequately informed or advised by experts to enable them to prevent the hazards that electricity may present.
• Trained person: A person with technical knowledge or experience (expert person), or who has received specific instructions sufficient to enable them to prevent electrical hazards, in relation to certain operations carried out under specified conditions (instructed person). The term trained is therefore an attribute relating to:
- the type of operation;
- the type of installation on which, or in the vicinity of which, the work is to be carried out;
- the environmental, contingent, and supervision conditions by more trained personnel.
• Untrained person: A person who is not expert and not instructed.
Loss of insulation between normally live conductors and exposed conductive parts can cause a fault called generally a ground fault.
The main causes of insulation loss are:
 |
decay of dielectric properties over time (cracks in insulating rubbers, etc.); |
 |
mechanical failure (e.g., the shearing of an underground cable by a mechanical shovel); |
 |
particularly aggressive environments (presence of dust, humidity, pollution, etc.); |
 |
localized electric arcs and resulting overheating. |
 |
rodent action; |
 |
disturbances to telecommunication systems; |
 |
erosion phenomena of electrical earth electrodes. |
Ground fault current initially manifests itself as a localized arc at the point where the insulation has failed; this arc is characterized by a very modest current intensity, in the order of a few tens of milliamps.
Subsequently, the fault evolves, more or less rapidly, to become a phase-to-ground fault. If this fault is not promptly interrupted by protection devices, it can affect all phases, resulting in a three-phase short circuit with contact to ground.
A first consequence of ground fault current is, therefore, the damage suffered by the system, both due to the modest initial arc currents, which are difficult to detect by overcurrent releases and can persist for a long time and trigger a fire, and due to the short circuit that develops after the integrity of the system itself has been compromised.
Another important consequence of ground fault current is the danger to people resulting from indirect contact, that is, from contact with exposed conductive parts that have accidentally become live due to the failure of the basic insulation.
Classification of Distribution Systems
The extent of a ground fault and the consequences resulting from contact with live exposed conductive parts are crucially linked to the state of the power system's neutral conductor and the method of connecting the exposed conductive parts to ground.
To properly select the right ground fault protection device, it is therefore necessary to understand the system's distribution system. The international standard IEC 60364-3 classifies electrical systems with a two-letter combination.
The first letter indicates the situation of the power supply system towards ground:
- T direct connection to earth of a point, in AC, usually the neutral;
- I isolation from earth, or connection to earth of a point, usually the neutral, via an impedance.
The second letter indicates the situation of the electrical system masses in respect of ground:
- T masses connected directly to earth;
- N masses connected to the earthed point of the power supply system.
Any following letters indicate the arrangement of the neutral and protective conductors:
- S neutral and protection functions performed by separate conductors;
- C neutral and protection functions performed by a single conductor (PEN conductor).
TT System
In the TT system the neutral and the masses are connected to two electrically independent earthing systems (Fig.1)

and the ground fault current then returns to the feeder node through the ground (Fig.2).

In systems of this type, the neutral is normally distributed and its function is to make the phase voltage available (e.g. 230 V), useful for powering single-phase loads in domestic systems.

and the ground fault current then returns to the feeder node through the ground (Fig.2).

In systems of this type, the neutral is normally distributed and its function is to make the phase voltage available (e.g. 230 V), useful for powering single-phase loads in domestic systems.
In the TN system, the neutral is connected directly to earth, while the exposed conductive parts are connected to the same earthing system as the neutral.
The TN electrical system is divided into three types depending on whether the neutral and protective conductors are separated or not:
1. TN-S: the neutral conductor (N) and the protective conductor (PE) are separated (Fig.3).

2 TN-C: the neutral and protection functions are combined in a single conductor called PEN (Fig. 4)

3 TN-C-S: the neutral and protection functions are partly combined in a single PEN conductor and partly separated PE + N (Fig. 5).

In TN systems the earth fault current returns to the power node through a direct metallic connection (PE or PEN conductor) without practically affecting the earth electrode (Fig. 6).

The IT electrical system has no active parts directly connected to earth but may have active parts connected to earth through a high impedance (Fig.7). All exposed conductive parts, individually or in groups, are connected to an independent earthing system.

The earth fault current returns to the power node through the earthing system of the masses and the capacitances to earth of the line conductors (Fig. 8).

Effects of current in the human body
The dangers arising from contact between a person and a live part arise from the consequent passage of current through the human body. These effects can be summarized as follows:
- Tetanization: the muscles affected by the passage of the current contract, making it difficult to detach from the live part. It should be noted that very high currents do not usually cause tetanization because when they pass through the body, muscle excitation is so high that involuntary muscle movements generally project the subject away from the source.
- Respiratory arrest: If an electrical current passes through the muscles that control the movement of the respiratory system, the involuntary contraction of these muscles disrupts the normal functioning of the respiratory system, and the person may suffocate or suffer trauma from asphyxiation.
- Ventricular fibrillation: This is the most dangerous effect and is caused by the overlapping of external currents with physiological ones, which, by generating uncoordinated contractions, causes the heart to lose its rhythm. This abnormality is called ventricular fibrillation and is particularly dangerous if ventricular because it becomes a non-reversible phenomenon, persisting even after the stimulus has ceased.
- Burns: These are caused by the heat generated by the Joule effect of the electric current flowing through the body.
Protection against indirect contact by automatic disconnection of the circuit
The standard requires automatic disconnection of power for protection against indirect contact.
The protective device must automatically disconnect the power supply so that, in the event of a fault, a prospective contact voltage exceeding the conventional limiting contact voltage of 50 V AC (25 V in special environments) cannot persist between a live part and an exposed conductive part or protective conductor for a duration sufficient to cause a risk of harmful physiological effects in a person in contact with simultaneously accessible parts.
This protective measure requires coordination between the system's earthing method and the characteristics of the protective conductors and protective devices.
Devices suitable for automatic power disconnection and capable of detecting earth-fault currents include:
- circuit breakers with thermomagnetic trip units;
- circuit breakers with microprocessor-based electronic trip units;
- circuit breakers with microprocessor-based electronic trip units with integrated earth-fault protection (function G);
- thermomagnetic or electronic circuit breakers with integrated residual current trip units;
- residual current circuit breakers;
- residual current relays.
As will be seen later, the protective device must be coordinated with the distribution system and the method of connecting the exposed conductive parts to earth so as to intervene in a timely manner to limit the duration of dangerous contact voltages present in the exposed conductive parts following the fault.
The following figure illustrates an example of the path of the earth fault current in a system where the neutral is directly connected to earth, while the exposed conductive parts are connected to the same earthing system as the neutral (TN system).

| Connection to ground |
Protection |
- The power source ground is separate from the utility ground.
- The phase conductor is separate from the ground conductor.
|
- Protection against current leakage is entrusted to differential switches
|
| Residential users |
Critical issues |
The TT system is common in residential homes, but:
- Connecting to the mains neutral isn't practical; I connect to a different grounding system.
- Safety depends heavily on the system's grounding impedance.
|
Risk of false tripping of RCDs, especially in the case of partial leakages, which do not lead to actual faults.
- If the grounding system is poor or poorly constructed, the risk of electrocution from indirect contact increases.
|
| Industrial/commercial users |
Critical issues |
The TT system is less common because it can be difficult to ensure grounding quality in humid or dusty environments:
- More difficult surge protection.
- More complicated power distribution, especially with high loads.
|
- Increased risk of frequent outages and false alarms due to leakage.
- Difficulty managing high fault currents in environments with sensitive industrial machinery
|
| Residential users |
Critical issues |
- The IT system is not widely used in residential homes due to the more complex systems and complex grounding management.
- Used in systems with high business continuity requirements (e.g., hospitals).
|
- Complex monitoring and the need for alarm systems to quickly identify faults.
- Risk of unnoticed outages - could cause damage to the electrical system if not managed properly.
|
| Industrial/commercial users |
Critical issues |
- Ideal for industrial and hospital applications where power continuity is critical.
- Hospitals, research laboratories, and high-tech facilities often use this configuration.
|
- In the event of a fault, the user does not receive an immediate notification – the system must be constantly monitored.
- Insulating the neutral wire makes fault detection more difficult, but at the same time reduces the risk of more serious faults such as short circuits.
|
Summary of critical issues by user type
| Residential users |
Industrial/Commercial Users |
| TT: Less expensive but less safe in the event of a leak. |
TT: Not ideal for high loads or complex systems. |
| TN: Safe, with adequate protection, but requires a well-designed earthing system. |
TN: Suitable for most industrial systems, but beware of the risk of neutral interruption. |
| IT: Complex and expensive, but ideal for fault-sensitive environments (hospitals, high-reliability systems). |
IT: Ideal for systems requiring absolute operational continuity, but requires advanced fault monitoring. |